QK32      QK SERIES INTELLIGENT CONTROLLER


QK32

Controller for three phase motor


THREE PHASE DIMENSIONS OF MOTOR UNIT:
Type
Three phase
Voltage 380v
Hz50
Motor
Power
Store
Current
Max
KW HP A
QK321 0.75 1 2.2
1.1 1.5 3
1.5 2 3.9
2.2 3 5.5
3 4 7.3
4 5.5 9.5
QK322 5.5 7.5 12.5
7.5 10 16.5
9.2 12.5 20
11 15 23.5
QK323 15 20 32
18.5 25 40

220v~240v/50Hz~60Hz

·Three phase motor intelligent controller

QK 32 Series intelligent controller ofr three phasw motor

  • suitable application range
    -Type of motor:Three phase capacitance motor
    -Motor power:0.75~18.5kW
    -Voltage:220v~240v/AC
    -Frequence:50Az~60Hz

  • Product functions
    -Protect against short circuit
    -Protect for over current
    -Protect against open phase
    -Protect against lightning strike
    -Protect against pump dry-running
    -Voltage-Current digital display

  • Technical characters
    -Manual/Auto-control
    -Double liquid level auto-control
    -Pulse electrode probe check

  • Technical index
    -Action time of short circute:<0.1sec.
    -Action time of open phase:<2sec.
    -Action time of over current:5sec.
    -Recovery time of over current:30min
    -Action time of dry-running protection:6sec.
    -Recovery time of dry-running:30min.
    -Double liquid level transfer distance:>1000m

  • Installation environment index
    -Grade of protection:IP20
    -Environment temperature:-25℃~+55℃
    -Environment humidity:(20~90)%RH
  • DIMENSION TABLE OF CABLE IN WELL
    The following table shows the max.Length from starter of motor to pump in well






  • If it used the star-delta connection to start the motor that the current will reduce(1×0.58),so the length of cable can increase(L×1.73)than the data in table.
    SIZE kW ln(A) 1.5
    mm2
    2.5
    mm2
    4
    mm2
    6
    mm2
    10
    mm2
    4" 0.37 4 111 185 295    
    0.55 5.8 80 133 211 315  
    0.75 7.5 58 96 153 229 377
    1.1 7.3 38 79 127 190 316
    1.5 10.2 34 57 92 137 228
    2.2 14   43 68 102 169

  • Three phase asynchronous submersible motor

  • 380~415v/50Hz
    SIZE kW In(A) 1.5
    mm2
    2.5
    mm2
    4
    mm2
    6
    mm2
    10
    mm2
    16
    mm2
    25
    mm2
    35
    mm2
    4" 0.37 1.4 768              
    0.55 2.2 489 811            
    0.75 2.3 416 691            
    1.1 3.4 281 467 744          
    1.5 4.2 219 363 579 862        
    2.2 5.5 153 254 405 605 997      
    6" 3 7.9 113 188 300 447 736      
    4 9.6 89 147 235 350 578 909    
    5.5 13.6 66 109 174 260 427 671    
    7.5 17.6 49 81 130 193 319 501 746  
    9.2 21.8   65 103 154 254 400 611 833
    11 24.8   56 89 133 219 345 526 719
    15 34     66 98 161 254 729 974
    18.5 42       80 132 208 317 432

  • If it used the star-delta connection to start the
    motor that the current will reduce(1×0.58),so the
    length of cable can increase(L×1.73)than the data
    in table.

  • For example in fact the current of submersible
    pump is lower than the load current 10%,the length
    of cable can be longer 10% than the data in table.
  • In order to reduce operating loss as far as
    possible,selected the cross section can much
    increase than the data in table.Especially for the
    condition which operating voltage is lower than rated
    voltage.